These fire pumps are designed and manufactured according to Standard No. 20 of the National Fire Protection Association (NFPA) of the USA.
| Pump Body | Split Case or Back Suction Type |
| Pump Body Material | GG25 or GGG40 Cast Iron |
| Impeller | GG25 Cast Iron or Bronze (CuSn7) |
| Shaft | AISI 420 Stainless Steel |
| Sealing | Gland Packing or Mechanical Seal |
| Closed Valve Pressure | Should not be more than 140% of the nominal pressure |
| Maximum Load | Minimum pressure at 150% flow rate should not be lower than 65% of the nominal pressure |
| Suction Collected Water Flowrate | Should not be less than 3 m/s |